Overcoming the limitations of existing ADPI assessment with AHC
Saturday, August 26, 2023
Overcoming the limitations of existing ADPI assessment with AHC
By
ganesh gund
Blog Author - Manish Kamath
Written by Ganesh Gund
Approximately
5 Minutes Reading
Approximately
5 Minutes Reading
When considering the criteria involved in designing an air distribution system main objective are thermal comfort of the occupants, offsetting of the room heat loads, supply of fresh air and energy efficiency etc. The performance of an air distribution system within a room/zone can be rated in terms of Air Diffusion Performance Index (ADPI). For selecting and placing air terminal outlets to achieve a spatially uniform air distribution and thermal environment in the room, the Air Diffusion Performance Index (ADPI) is quite commonly used. The objective of this blog to clarify the application of ADPI, its formulation, implementation, limitations and relevance to the industry standards and use of Autonomous HVAC CFD (AHC) to overcome the limitations of existing ADPI Assessment, this enables designers to effectively use this tool without compromising their initial design.
What is ADPI?
ADPI is used as a measure to evaluate the performance of an air distribution system within a room/zone. Its value dependent on several factors as follows: 
  • Room dimensions
  • Room loads
  • Air distribution products type
  • Air distribution lay-out of air inlets and outlet
  • Throw distances of air registers
ADPI is defined as a percentage of the measurements taken within an occupied space where the effective draft temperature is between -1.7 oC to + 1.1 oC  with the air velocity less than 0.35m/s (ASHRAE Fundamentals, 2001). An ADPI of 100% implies the measurements taken at all the sampling points within the occupied zone conform to the given criteria above, and therefore the thermal condition in that space is expected to be at an acceptable level. Most air distribution systems are designed to achieve ADPI of 80% or greater (ASHRAE Fundamentals-2001).
What it is Not?
ADPI is not a performance index for an individual air terminal device or air register such as a diffuser, an air grille or a jet nozzle etc. Hence, stand-alone air distribution air registers cannot be rated for ADPI. It is not a valid concept for air distribution product manufacturers to provide test data or certification for ADPI for individual air registers, because it is not a product performance test standard.  
ADPI should not be used as a basis on which to judge thermal comfort in a general sense where industry standards such as PMV and PPD are used as benchmarks. The reason for this is because ADPI does not take into consideration the humidity and radiant temperatures of the surrounding surfaces in the space considered, two other environmental factors determining thermal comfort. Furthermore, metabolic rate and clothing insulation of the occupants are two additional personal variables the PMV and PPD indexes take into account for a complete and in-depth assessment of thermal comfort.
ADPI Formulation
  1. Determination of Effective Draft Temperature
θ = (tx – tc ) – 8(Vx – 0.15)
were:
 θ – Effective draft temperature (K)
 tx – Local air stream dry-bulb temperature (°C)
 tc – Average (set-point) room dry-bulb temperature (°C)
 Vx – Local airstream centerline velocity (m/s)
  1. Determination of ADPI
ADPI = (N θ ⁄ N) × 100%
were:
N θ - Number of points measured in the occupied space that falls within -1.7 oC < θ <+ 1.1 o
N – Total number of points measured in the occupied space
Conventional ADPI selection process and its limitations 
Diffuser selection and spacing determination using the ADPI method for design it is one of the selection methods prescribed in ASHRAE for diffuser selection, specifically for determining the spacing between adjacent diffusers and its procedure as follows: 
  1. Select type of diffuser.
  2. Check Manufacturer’s recommendations to determine if the diffuser’s jet pattern will have      excessive drop at the desired flow rate, using ceiling height as a parameter
  3. Select the characteristic length (L) from the plans. This is the distance from a diffuser to a wall, or to the centerline between two diffusers, etc.
  4. Determine the desired diffuser (isothermal) throw using the characteristic room length and the throw ratio from Table 1.
  5. From the manufacturer’s performance table select a size with a T50 within range for the diffuser at the required cfm.
  6. With the VAV system, this must be done for both maximum flow rate at maximum loads and at the lowest turn down flow rate when the space is occupied.
Example 
10’ x 10’ Office
24” x 24” Square Ceiling Diffuser 
100 cfm / 55oF Supply
6” Dia. Supply
75oF Space
Manuf. Specs
Isothermal Throw = 4’@ 50 fpm terminal velocity ( T 50 )
T 50 / L = 0.75
 Low Limit = ADPI Table > 80%
Diffuser Diffuser Dimension


Manufacturer catalogue
Fig: Manufacturer catalogue
2019 ASHRAE Applications Ch. 58
Table:1 2019 ASHRAE Applications Ch. 58
Many believe this selection is thought to result in high perceived comfort and ventilation mixing for the application. In light of the ADPI selection process above, it is not possible to evaluate the performance of a type of ventilation grille or diffuser and give it an ADPI rating based solely on its individual aerodynamic performance. As described, ADPI is intended to evaluate the performance of an air distribution system rather than the product alone. The resultant ADPI varies with room size and geometry, type of air terminal unit used, air outlet location relative to the walls and each other, and the way they are installed. 
Also, above tables have some limitations such as applicable for up to 12’ ceiling heights, depends on space heating & cooling loads (designer loads vary with weather location, occupancy type, energy code / building insulation and construction, etc.), depends on manufacturer’s diffuser throw data but this can vary between manufacturers, cooling ADPI tables are different from heating ADPI tables, methods don’t consider return grille location into account, May not effectively predict ADPI values for rooms with multiple diffusers, irregularly shaped spaces, multi-level spaces Therefore, each air distribution system within a space is unique and possesses its own ADPI. The same air distribution system in a different space may have a totally different ADPI.
How Autonomous HVAC CFD overcomes the limitations of exiting ADPI assessment and improve accuracy 
The Autonomous HVAC CFD (AHC) is an autonomous cloud-based CFD simulation web application developed to evaluate the performance of your HVAC systems without having any prior knowledge of CFD. AHC provides users with an efficient way of creating a design layout and simulating the space for different air distribution systems.
AHC offers two approaches for ADPI Values
  1. Standard Test Position Approach: ADPI rating is calculated as per ASHRAE Standard 113-Method of Testing for Room Air Diffusion.
  2. Volume Weighted Approach: ADPI rating is calculated based on the effective draft temperature and air speed values in every cell (small volume within the simulation domain) in the occupied zone, rather than just a few test positions.
Standard Test Position Approach
Fig: Standard Test Position Approach
Volume Weighted Approach
Fig: Volume Weighted Approach
Enhancing ADPI Accuracy in AHC through following Key Factors - 
  1. Probe Location & Measurement: - AHC Uses the probe locations, measurement guidelines as mentioned in ASHRAE 113-Method of Testing for Room Air Diffusion which helps to get ADPI values closer to as build design.
  2. Heat loads, design and performance of outlets: -Local sources of heat loads cause convection currents and stratification that determine the type, location, design and performance of the supply outlets. All these in turn may change/deviate the behavior of the original air distribution system at design stage. In AHC we are able to consider all these parameters while calculating ADPI values.
  3. Room geometry, interior design & ceiling heights: - The spacing of diffusers is influenced by the interior design, spatial constraints and room geometry etc., which will affect air flow patterns in the room. In AHC we are able to capture the effects of all this on ADPI values.
  4. Return air outlet location: - Its causes to short circuiting of supply air, which will compromise air distribution into the occupied zone in a similar fashion effective delivery of fresh air into the breathing zone of the room is compromised in an ACE evaluation. Particularly detrimental is the ceiling inlet & ceiling outlet set-up of entertainment air distribution because supply air is likely to exit out of the room through the return outlet before it gets mixed and delivered further into the room. 
  5. Different Scenario: - In VAV systems under turndown conditions, fixed diffusers with lower velocities such as the conventional four-way ceiling diffuser do not perform well and it affects the Final ADPI Value. In AHC we are able to get ADPI Value when VAV system work at maximum flow rate at maximum loads and at the lowest turn down flow rate at minimum load with VAV System
ADPI Test Case
Project Information
Location: Winter Haven, Florida
Application: Cooling
Outdoor Design Conditions: ASHRAE 0.4 %
Indoor Design Conditions:  Temperature- 75F, Relative Humidity- 50%
Ceiling Height: 12’
Occupancy - 32 Nos
Lights:  50W LED 2’ x 2’, centered 6 Nos
HVAC Load Details: 6 Tons Vs 2100 CFM 
Diffuser Selection:  2’ x 2’- 350 CFM 6 Nos
 
2D Layout- Burger Joint
Fig: 2D Layout- Burger Joint
 
Validation 01 - ADPI at different return air outlet location
 
ADPI at different return air outlet location
ADPI at different return air outlet location
ADPI at different return air outlet location
Fig: Original Design
 
Modified Design
Modified Design
Modified Design
Fig: Modified Design
 
Validation 02 - ADPI at Maximum & Minimum Load
 
ADPI at Full Occupancy
ADPI at Full Occupancy
Fig: ADPI at Full Occupancy
 
ADPI at Half Occupancy
ADPI at Half Occupancy
Fig: ADPI at Half Occupancy
References 
  1. ASHRAE Application Handbook 2019
  2. The truth about the Air Diffusion Performance Index (ADPI)-Eddy Rusly, M.AIRAH, and Steven Gagliardini, TROX Australia
  3. Titus engineering guidelines basic principles of air distribution
  4. ASHRAE 113 -Method of Testing for Room Air Diffusion
Get your FREE trial
Wish to explore Autonomous HVAC CFD to optimize your HVAC design for IAQ and thermal? Sign-up now and get free credits worth $500 for 90 days. You can explore the product and evaluate HVAC designs for Indoor Air Quality and estimate thermal comfort upto space area of 5000 square feet.
Blog Author - Ganesh Gund
Ganesh Gund
Ganesh is an HVAC Design Engineer at the Centre for Computational Technologies Private Limited (CCTech), Pune. He loves to work in the fields of Heating Ventilation & Air Conditioning (HVAC). He holds a Bachelor's degree in Mechanical Engineering from Savitribai Phule Pune University. His areas of interest are designing HVAC Systems for Residential, Commercial, Hospital, Cleanrooms, and Industrial Applications, Thermal Comfort, Indoor Air Quality, Energy Modelling Green buildings, and Energy Efficiency. Watching Cricket, traveling, and Swimming is his hobby and he likes to explore nature.
Blog Author - Ganesh Gund
Ganesh Gund
Ganesh is an HVAC Design Engineer at the Centre for Computational Technologies Private Limited (CCTech), Pune. He loves to work in the fields of Heating Ventilation & Air Conditioning (HVAC). He holds a Bachelor's degree in Mechanical Engineering from Savitribai Phule Pune University. His areas of interest are designing HVAC Systems for Residential, Commercial, Hospital, Cleanrooms, and Industrial Applications, Thermal Comfort, Indoor Air Quality, Energy Modelling Green buildings, and Energy Efficiency. Watching Cricket, traveling, and Swimming is his hobby and he likes to explore nature.
Comments